CU/XLPE/CUW/LEAD/PE - 132 KV (145 KV)
|
|
Dimensional Data
| [mm²] |
[mm²]** |
[mm] |
[mm] |
[mm] |
[mm] |
[mm] |
[mm] |
[kg/km] |
| 500 |
364 |
26.7 |
20.3 |
69.8 |
2.5 |
4.50 |
96 |
20700 |
| 630 |
364 |
30.4 |
20.3 |
73.8 |
2.5 |
4.50 |
100 |
22700 |
| 800 |
359 |
33.7 |
20.3 |
77.1 |
2.5 |
4.50 |
103 |
24800 |
| 1000 * |
354 |
41.0 |
20.3 |
84.4 |
2.5 |
4.50 |
110 |
28400 |
| 1200 * |
354 |
44.0 |
20.3 |
87.4 |
2.5 |
4.50 |
113 |
30500 |
| 1600 * |
349 |
50.0 |
20.3 |
93.4 |
2.5 |
4.50 |
119 |
34700 |
| 2000 * |
344 |
56.0 |
20.3 |
99.4 |
2.5 |
4.50 |
125 |
39600 |
|
* Round Segmental Conductor.
** Specified size of CUW screen along with the LEAD sheath shall withstand 40 kA for 3 sec.
*** Specified nominal thickness of insulation as per AEIC CS7 as required by SEC-SOA.[for special constructions, screen area may vary slightly]
Electrical Data
| 500 |
0.0366 |
0.0498 |
0.44 |
0.78 |
0.15 |
41.30 |
40 |
421 |
509 |
581 |
720 |
809 |
910 |
| 630 |
0.0283 |
0.0401 |
0.43 |
0.75 |
0.16 |
52.04 |
40 |
455 |
571 |
656 |
804 |
926 |
1052 |
| 800 |
0.0221 |
0.0331 |
0.41 |
0.73 |
0.17 |
66.09 |
40 |
485 |
629 |
731 |
879 |
1039 |
1195 |
| 1000 |
0.0176 |
0.0238 |
0.39 |
0.69 |
0.19 |
82.61 |
40 |
536 |
744 |
863 |
1023 |
1275 |
1469 |
| 1200 |
0.0151 |
0.0208 |
0.38 |
0.68 |
0.20 |
99.13 |
40 |
555 |
793 |
928 |
1081 |
1380 |
1605 |
| 1600 |
0.0113 |
0.0165 |
0.36 |
0.65 |
0.22 |
132.17 |
40 |
589 |
886 |
1056 |
1188 |
1586 |
1881 |
| 2000 |
0.0090 |
0.0140 |
0.35 |
0.63 |
0.24 |
165.22 |
40 |
613 |
956 |
1159 |
1273 |
1756 |
2123 |
|
* Maximum permissible non-adiabatic short circuit current as per IEC 949 for both CUW & LEAD sheath
** Flat formation with both ends bonded system is not recommended
Laying Conditions
| - Ground Temperature |
35 |
°C |
| - Ground Thermal Resistivity |
2.0 |
K.m/W |
| - Laying Depth |
1500 |
mm |
|
|
| - Air Temperature |
50 |
°C |
| - Number of Circuits |
1 |
circuit |
| - Distance between Conductors (flat) |
400 |
mm |
|
|