| » Energy Cables |
| » |
Wires
|
| » |
LV Cables
|
| » |
Control Cables
|
| » |
LV Lead Sheathed
|
| » |
LSF Cables
|
| » |
MV Cables
|
| » |
MV Lead Sheathed
|
| » |
HV Cables
|
| » |
Overhead Lines
|
|
|
| » Communication |
| » |
Telephone Cables
|
| » |
Optical Fibre Cables
|
|
|
| » |
Copper Rods
|
| » |
PVC Compounds
|
|
|
| NOTICE!
RCGC catalogues under circulation are still valid. Some International and National Standards mentioned in RCGC Catalogues.. <more>
|
|
|
 |
 |
 |
|
|
|
|
[ + ]
-
[ - ] |
|
Conductors
Conductors shall be Round Stranded (Non-compacted or Compacted) or shaped, Class 2 as per IEC 60228. For smaller sizes up to and including 4 mm2, Solid Conductors, Class 1 to IEC 60228 can also be provided based on special request.
Insulation
XLPE Insulation material and thickness shall be as per IEC 60502-1 rated for 90°C continuos operation.
PVC Insulation material and thickness shall be as per IEC 60502-1 and BS 6346. PVC material shall be Type A as per IEC 60502-1 or TI1 as per BS 6346.
PVC Insulation material as per SASO 1694 rated for 85°C continuous operation is also available upon special request.
Colour Code
Colour code (1) is followed by all utilities in the Middle East and colour of insulation for cables shall be as per mentioned below. However, cables as per colour code (2) mentioned below can also be provided based on special request.
|
Colour Code (1) :
| 1 Core |
: |
Red or Black |
| 2 Cores |
: |
Red, Black |
| 3 Cores |
: |
Red, Yellow, Blue |
| 4 Cores |
: |
Red, Yellow, Blue, Black |
| 5 Cores |
: |
Red, Yellow, Blue, Black, Green |
| Above 5 Cores |
: |
Black Cores with White numerals |
Colour Code (2) :
| 1 Core |
: |
Brown or Blue |
| 2 Cores |
: |
Brown or Blue |
| 3 Cores |
: |
Brown, Black, Grey |
| 4 Cores |
: |
Blue, Brown, Black, Grey |
| 5 Cores |
: |
Green/Yellow, Blue, Brown, Black, Grey |
| Above 5 Cores |
: |
Black Cores with White numerals |
Assembly / Inner Sheath
Two, Three or Four insulated conductors are laid-up together with non-hygroscopic fillers compatible with the insulation material and the assembly is bedded with an extruded layer of PVC.
Lead Sheath
Extruded lead Alloy Type "E" to BS 12548. Thickness of lead shall be as per IEC 60502-1. Cables with other thickness of Lead Sheath can also be provided based on specific request.
|
|
|
Types of LV Lead Sheathed
|
|
01..
|
|
|
|
|
02..
|
|
|
|
|
03..
|
|
|
|
|
04..
|
|
|
|
|
05..
|
|
|
|
|
06..
|
|
|
|
|
07..
|
|
|
|
|
08..
|
|
|
|
|
09..
|
|
|
|
|
10..
|
|
|
|
|
|
|
Armour
Armour Shall compromise of either : Galvanized Steel Wires in accordance with IEC 60502-1 or BS 6346 or BS 5467 laid helically over PVC bedding as per requirement.
Galvanized Steel Tapes applied helically over PVC bedding in accordance with IEC 60502-1.
Outer Sheath
Outer sheath shall be of Extruded PVC Type ST2 as per IEC 60502-1 or Type 9 as BS 6346/5467. Special type ov PVC sheathing material such as Fire Retardant PVC, Anti-Termite PVC, Anti-Rodent PVC, Sunlight resistant PVC, Oil Resistant PVC are available on special request. Also, special sheathing materials such as LLDPE, MDPE, HDPE, LSF, CPE are available on request.
|
|
|
|
|
|
 |
 |
|
 |
|