ARMOURED THREE CORE LEAD SHEATHED CABLE
COPPER CONDUCTORS STANDARD : IEC 60502-2 Uo/U (Um)=6/10(12) kV

ARMOURED THREE CORE LEAD SHEATHED CABLE

Code Number (1) Nominal Cross Section Nominal Dia. of Cond. Weight of Cond. Nominal Insulation Thick. Approx. diameter over insulation Nominal Lead Sheath Thick. Armour Steel Wire Dia. Nominal PVC Sheath Thick. Approx. External Diameter Approx. Weight of Cable
  mm² mm kg/km mm mm mm mm mm mm kg/km
10 25 5.9 670 3.4 13.9 1.7 2.5 2.6 58 7800
11 35 6.9 929 3.4 14.9 1.8 2.5 2.7 62 8750
12 50 8.1 1260 3.4 16.1 1.9 2.5 2.8 65 9650
13 70 9.7 1820 3.4 17.7 2.0 2.5 2.9 69 11100
14 95 11.4 2518 3.4 19.4 2.1 2.5 3.1 74 13000
15 120 12.9 3175 3.4 20.9 2.2 2.5 3.2 79 14750
16 150 14.3 3919 3.4 22.3 2.3 3.15 3.3 84 17250
17 185 16.0 4902 3.4 24.0 2.4 3.15 3.5 88 19500
18 240 18.4 6443 3.4 26.4 2.5 3.15 3.7 96 22950
19 300 20.7 8069 3.4 28.9 2.6 3.15 3.8 102 26300

Nominal Cross Section DC Resistance at 20°C Nominal Inductance Capacitance Short circuit current for 1 sec. Current Carrying Capacity(3) Voltage drop per phase

Conductor
Screen per phase (2) Under- ground Cable Cable in Air
mm² ohm/km mH/km mF/km KA KA A A V/A/km
25 0.727 0.387 0.21 3.575 0.503 150 150 0.829
35 0.524 0.368 0.23 5.005 0.535 190 190 0.618
50 0.387 0.355 0.25 7.150 0.574 225 225 0.146
70 0.268 0.342 0.29 10.010 0.625 270 280 0.351
95 0.193 0.335 0.31 13.585 0.680 330 340 0.273
120 0.153 0.326 0.34 17.160 0.728 370 385 0.231
150 0.124 0.319 0.37 21.450 0.773 420 445 0.200
185 0.0991 0.313 0.40 26.455 0.827 470 510 0.173
240 0.0754 0.305 0.44 34.320 0.917 540 590 0.148
300 0.0601 0.297 0.48 42.900 0.997 580 620 0.131


  1. The code numbers to be read in conjuction with 03020123 at the beginning and "L" at the end.

    Example: for 150 mm² the code number is 0302012316L

    Code number for different types of insulation screen : replace the 6th digit as follows:
    2 for S + CUW; 3 for B + CUT; 4 for B + CUW; 5 for G + CUT and 6 for G + CUW

  2. For Copper Tape screen only.

  3. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

    For other laying conditions, please refer to Table nos. 1 - 5 for derating factors.
   





XLPE INSULATED LEAD SHEATHED MEDIUM VOLTAGE CABLES